In preparationFacilities & Security Operations · Owner: Mariam A. · Working version 0.9
Tender Readiness Review
Review findings against the project brief and configured demonstration template. These are not official Ministry policy checks.
mandatory elements present
Structural checks · POC configurationtechnical confirmations needed
Department input requiredtemplate conflicts
Selected demonstration templateRetention requirement needs an acceptance test
06 · Testing and commissioning
WHY IT MATTERSThe retention requirement must be confirmed and linked to a measurable acceptance test. A storage capacity statement alone does not demonstrate retention.
REQUIRED HUMAN ACTIONConfirm TR-014, then add a witnessed retention verification step to the acceptance criteria.
External camera locations are unconfirmed
04 · Technical requirements
WHY IT MATTERSThe final external camera count is missing. Suppliers cannot price a consistent installation scope without an approved location plan.
REQUIRED HUMAN ACTIONConfirm the external camera count and reference an approved demonstration location plan.
Warranty term differs from the selected template
11 · Commercial response structure
WHY IT MATTERSThe working draft specifies 24 months; the selected demonstration template calls for 36 months. Inconsistent terms prevent comparable proposals.
REQUIRED HUMAN ACTIONApply the demonstration template warranty of 36 months and record the reviewer rationale.
Delivery period has not been confirmed
05 · Installation requirements
WHY IT MATTERSWithout a confirmed delivery window, suppliers cannot plan comparable implementation schedules.
REQUIRED HUMAN ACTIONObtain a delivery period from the requesting department and record the confirmed value.